JCLT Differential Pressure Level Transmitter

JCLT Differential Pressure Level Transmitter is a transmitter for pressure and flow measurement applications.

JCLT Differential Pressure Level Transmitter

JCLT Differential Pressure Level Transmitter  is a transmitter for pressure and flow measurement applications.

Feature 

Updating time of output current in 200 ms

Improved performance, increased accuracy and greater stability

Two years stability of 0.15%

0.1% accuracy

Parameter setting by keypad directly

4-20 mA output plus direct digital HART communication

Automatic zero calibration by push-button

Explosion proof and weather proof housing

Technical Parameter 

Process Fluid : Liquid, Gas of Vapor

Display : 5 Digits programmable & 0-100% Bargraph

Application : Liquid Level, Differential Pressure,

Display Unit : Standard 22 different engineering unit

Gauge Pressure, Absolute Pressure 5 Digits programmable for special unit

Measuring Range : 0 – 6.0 kPa ~ 0 – 40 kPa (Minimum)

Keypad : 3 internal keys for programming

: 0 – 4.0 MPa ~ 0 – 20.0 MPa (Maximum) and output setting

Turndown Ratio : 40 : 1 Current Output : 4 – 20 mA 2 wires

Accuracy : +/- 0.075% of span with Hart Signal (Compatible)

Stability : +/-0.15% of URL for 2 years Load : Rohm=(Vdc-9)*50

Working Temperature : -40 to +250 °C Power Supply : 9 – 36 VDC

Max. Pressure : 40 MPa (Dependent on flange rating)

Digital Communication : Hart Protocol                   Material Damping : 0 – 32 seconds

Flange/Adapter : Carbon Steel / Stainless Steel 304 /

Response Time : 100 mS

Stainless Steel 316                Turn on Time : 2 Seconds with minimum damping

Diaphragm : Stainless Steel 316L / Hastelloy B /

Zero Calibration : Automatic calibration by push-button

Hastelloy C / Monel / Tantalum Cable Entry : 1/2″ NPT(Female) / M20 Conduit Threads

Bolts & Nuts : Carbon Steel / Stainless Steel 316

Temperature Effect : +/-0.18% ~ +/-0.5% of span per 20 °C

Name / Tag Plate : Stainless Steel 304 / Stainless Steel 316 EMI/RFI

Effect : Follow SAMA PMC 33.1 from 20 to 1000

Fill Fluid : Silicone / High Temperature Silicone

High Pressure Side : 1-1/2″, 2″, 3″, 4″ Flanges

Fluorine Oil / Vegetable Oil ANSI / DIN / JIS / Tri-Clamp

Protection Class : IP67 (Standard) Extended Diaphragm : 2″, 4″, 6″ length

Intrinsically Safe EEx ia IIC T5 (Standard) Low Pressure Side : 1/4″ – 18 NPT , 1/2″ – 14 NPT

Explosion proof Ex D IIB T5 Ambient Temperature : -25 to +85 °C

Dimensions : 102 mm (W) * 188 mm (H) * 189 mm (D)

Weight : 8 – 21 Kg

Smart Differential Pressure level Transmitter
JCLT
Pressure range 4 0 – 6.0 (0.4) kPa … 0 – 40 kPa
5 0 – 40 (2.0) kPa … 0 – 200 kPa
6 0 – 160 (10.0) kPa … 0 – 1000 kPa
7 0 – 400 (25.0) kPa … 0 – 2500 kPa
8 0 – 1.6 (0.08) MPa … 0 – 8.0 MPa
9 0 – 4.0 (0.20) MPa … 0 – 20 MPa
Process

Connection

1 PN10
2 PN16
3 PN25
4 PN40
A ANSI 150#
B ANSI 300#
J JIS 10K
K JIS 20K
Z Other
Flange Rating 1 1-1/2″ (Diaphragm Diameter If Extended: 38mm)
2 2″ (Diaphragm Diameter If Extended: 48mm)
3 3″ (Diaphragm Diameter If Extended: 66mm)
4 4″ (Diaphragm Diameter If Extended: 89mm)
Diaphragm Extension Length 0 Flush Diaphragm
2 2″ (50mm)
4 4″ (100mm)
6 6″ (150mm)
Diaphragm Material N Stainless Steel 316L
B Hastelloy B
C Hastelloy C
T Tantalum
Flange Material N Carbon Steel
4 Stainless Steel 304
5 Stainless Steel 316
Low Pressure Side Process Connection N 1/4″ – 18 NPT
A 1/2″ – 14 NPT(with Adapter)
Z Other
Explosion-proof N Exd IICT 6
S Intrinsically Safe Exib II CT5
Fill Fluid N Silicone (Max. Temperature 130 °C)
S HT Silicone (Max. Temperature 250 °C)
F Fluorine (Max. Temperature 160 °C)
V Vegetable Oil (Max. Temperature 130 °C)
Cable Entry N M20 Conduit Threads
P 1/2″ NPT (Female)

Related Products

Scroll to Top